I have a SBG IMU/GPS sensor that is working well in most of the configuration I have made for it.  I'm struggling to get the UTC H/M/S out of it, however the RAW channels logged in my ICD appear to be correct according to what the SGB manual states.
 
I have them configured in the input stream as:
Screenshot 2023-11-05 at 2.30.42 PM.png
The UTC Min channel has a unit of min, UTC Sec of second, even tho their details aren't in the screen shot
 
When I display the calibrated channel in Toolbox, I get values I can't quite make sense of
                 Raw          Calibrated (s)
Hour.        14.            224  
Min.          12.           208
Sec.           52.           52
 
The actual time was indeed around 8:12 am  in UTC-6
 
If I switch the default unit in Toolbox for the Hour from  seconds to hours, I get ~0.  Similarly for Minute.  Seconds appears to be working correctly.
 
Is there a way to get the calibrated values correct?  I can simply use the raw value but would like to understand what the calibration is doing here that I'm not quite following.  TIA.
Reply 0 0
littleozfella
In hours make the gain 0.0625  (16 * 14 = 224)      For Hours try multiplier  0.05769 and see if that works, it seems a strange multiplier but give it a go.  Doesn't the data sheet for the device give you a multiplier (gain) and adder if required?
 
Cheers
Reply 0 0
leisurehound
In hours make the gain 0.0625  (16 * 14 = 224)      For Hours try multiplier  0.05769 and see if that works, it seems a strange multiplier but give it a go.  Doesn't the data sheet for the device give you a multiplier (gain) and adder if required?
 
Cheers
Indeed it does give me the multiplier (image attached below).  It specifies a scaling of 1 and the raw value in Toolbox is showing its sending it as expected.  There is something in Cosworth that is calibrating into the numbers I'm seeing via the units that I don't quite understand/expect.
 
Screenshot 2023-11-06 at 6.45.49 AM.png
Reply 0 0
littleozfella
Have you tried unix time?? or maybe test as signed data (S8)  